PARTICLE ALLERGENS (Airborne Particulate Matter - PM)

 Sensor Reporting Range: 0 - 50 ug/m3

Alert Criteria (Standard)* Indoor Air Quality Rating
0 - 10 ug/m3, daily average Acceptable
11 - 25 ug/m3, daily average Action Recommended for Sensitive Groups***
26 - 35 ug/m3, daily average Action Recommended
>35 ug/m3, daily average Action Necessary

Rationale: Acceptable particulate matter (PM) values are based on the lack of two major indoor PM sources: environmental tobacco smoke and cooking. Extensive evidence shows that even limited exposure to low PM levels can trigger or worsen asthma, allergies, or other symptoms in sensitive populations. Chronic exposures are highly correlated to chronic lung disease and reduced lung capacity in both adults and children. Short- and long-term PM exposure at any level can result in respiratory, eye, and mucous membrane irritation for any population, but sensitive groups are shown to be definitively at risk for marked adverse affects.

* Standard alert criteria is based on scientific literature produced by ASHRAE, Health Canada, Indoor Air Quality Association, World Health Organization, California Air Resources Board, LEED and EPA.

CHEMICAL POLLUTANTS (Total Volatile Organic Compounds - TVOCs)

Sensor Reporting Range: 0 - 4000 ug/m3

Alert Criteria (Standard)* Indoor Air Quality Rating
0 - 500 ug/m3, daily average Acceptable
501 - 3000 ug/m3, daily average Action Recommended for Sensitive Groups***
>3000 ug/m3, daily average Action Necessary

Rationale: Acceptable total volatile organic compound (TVOC) values are based on threshold response levels to mixtures of compounds. At low levels, VOCs are known to trigger or worsen asthma, allergy, and other adverse systems in sensitive populations. Respiratory, eye, skin, and mucous membrane irritation can occur. Some VOCs are known carcinogens. Both short- and long-term exposure to VOCs create risk for both sensitive and healthy populations, with total responses and percent of affected population increasing in conjunction with VOC level increases.

* Standard alert criteria is based on scientific literature produced by ASHRAE, Health Canada, Lars Molhave, Indoor Air Quality Association, European Union, Washington State, EPA.

CARBON DIOXIDE (CO2)

Sensor Reporting Range: 0 - 2000 ppm

Alert Criteria (Standard)* Indoor Air Quality Rating
0 - 750 ppm, daily average Acceptable
751 - 999 ppm, daily average Action Recommended for Sensitive Groups***
>999 ppm, daily average Action Necessary

Rationale: Acceptable carbon dioxide (CO2) levels are based on ambient backgrounds levels measured outdoors. Concentrations above ambient (300-450 ppm) generally occur from human occupancy and activity combined with lack of adequate ventilation. This can lead to health and comfort issues such as fatigue and/or a perception of "stale air." Above 1000 ppm daily average, CO2 can cause dizziness, fatigue, and headache for much of the population.

* Standard alert criteria is based on scientific literature produced by ASHRAE, Health Canada, Indoor Air Quality Association, and LEED.

TEMPERATURE SUMMER

Sensor Reporting Range: 32°F - 100°F

Alert Criteria (Standard)* Indoor Air Quality Rating
72°F - 78°F Acceptable
<72°F or >78°F for 1 hour or more Action Recommended for Sensitive Groups***
<72°F or >78°F for 1 day or more Action Recommended
<72°F or >78°F for duration of test Action Necessary

TEMPERATURE SUMMER

Alert Criteria (Standard)* Indoor Air Quality Rating
68°F - 75°F Acceptable
<68°F or >75°F for 1 hour or more Action Recommended for Sensitive Groups***
<68°F or >75°F for 1 day or more Action Recommended
<68°F or >75°F for duration of test Action Necessary

Rationale: Temperatures that are too high, too low, or inconsistent can stress the body as well as cause discomfort. Sensitive groups may be immediately affected by temperature fluctuations as little as a single degree. Potential impact on human comfort of limited (1 day or more) or extended (duration of test) temperature values outside the acceptable range support recommended and/or necessary action, as well as indicate poorly functioning, absent, or improperly installed equipment.

* Standard alert criteria is based on scientific literature produced by ASHRAE, Health Canada, Indoor Air Quality Association, and Washington State Dept. of Health.

HUMIDITY (RH)

Sensor Reporting Range: 10% - 90%

Alert Criteria (Standard)* Indoor Air Quality Rating
30% - 55%** Acceptable
<30% or >55% for 1 hour or more** Action Recommended for Sensitive Groups***
<30% or >55% for 1 day or more** Action Recommended
<30% or >55% for duration of test** Action Necessary

Rationale: Acceptable relative humidity (RH) values are based on both comfort and health reasons. Sensitive groups may be exposed to conditions where respiratory, skin, or other conditions are exacerbated via dryness, moistness, and/or microbial growth. Prolonged exposure for all populations to low level RH (<25%) and high levels (>60%) can increase the risk of microbial growth.

* Standard alert criteria is based on scientific literature produced by ASHRAE, UK Dept. of Health, World Health Organization, California Air Resourced Board, Indoor Air Quality Association, LEED and EPA.

CARBON MONOXIDE (CO)

Sensor Reporting Range: 0 - 100 ppm

Alert Criteria (Standard)* Indoor Air Quality Rating
0 - 5 ppm, 8-hour average Acceptable
5 - 9 ppm, 8-hour average Action Recommended for Sensitive Groups***
>20 ppm, 1-hour average &/OR >9 ppm, 8-hour average Action Necessary

Rationale: Acceptable carbon monoxide (CO) levels are based on adverse affects on human health from prolonged exposure to high levels of CO. Carbon monoxide is made naturally in the body, with COHb blood levels found at up to 2.5% without sign of adverse effects. Above 5 ppm, COHb levels increase above 2.5%, which can adversely affect cardiovascular disease sufferers as well as pregnant women and their unborn child. Healthy individuals will be impacted at levels of 12-20 ppm, including reducing breathing capacity among other effects. CO occurring at above 20 ppm for a 1-hr average has a severe impact on sensitive groups and significantly impacts healthy individuals as well. At high levels, carbon monoxide can cause death.

*Standard alert criteria is based on scientific literature produced by ASHRAEUK Dept. of HealthWorld Health OrganizationCalifornia Air Resourced BoardIndoor Air Quality AssociationLEED and EPA.